Your home’s systems

  1. Your AC got its fall tune-up. We cleaned the outdoor coil, tightened the electrical connections, and replaced the air filter. Everything tested normal. One part, the contactor, is starting to wear, so we’ll plan to replace it at your spring visit.

    Work done

    • Cleaned the outdoor coil (heavy cottonwood buildup)
    • Tightened the contactor connections
    • Tested the run capacitor: 44.6 µF and 4.9 µF, both in spec
    • Replaced the air filter

    Parts

    Air filter, 16 × 25 × 1

    Refrigerant

    None added

    Readings

    Suction

    118 psi

    Head

    310 psi

    Superheat

    11 °F

    Subcool

    9 °F

    Supply air

    55 °F

    Return air

    75 °F

    Found: Contactor is pitted and starting to wear
    • The outdoor unit after the visit
    • The unit's service tag
    • The technician photographing the data plate

    Approved and signed by Marcus R. on Nov 4, 2026. Records can be corrected, never erased; every version is kept.